Silica Gel Chillers

Silica Gel Chillers
Technical Data

eCoo 10

Article no. A700030/A700045

Application range
Hot water temperature 50 – 95°C
Re-cooling water temperature 22 – 40°C
Chilled water temperature 8 – 21°C
Performance data
Cooling capacity bis zu 16,7 kW
COPTH* max. 0.65
Dimensions
W x D x H 875 mm x 765 mm x 2.004 mm
Footprint 0.67 m2
Hot water circuit
Volume flow rate 2.50 m³/h
Available delivery head 464 mbar
Max. operating pressure 4 bar
Connection G 1 ¼” AG
Electrical power consumption / connection
At pressure drop 260 W
At max. delivery head 684 W
Electrical connection 230 V, 50/60 Hz
Weight
Weight (empty) ca. 370 kg*
Re-cooling circuit
Volume flow rate 5.10 m³/h
Available delivery head 690 mbar
Max. operating pressure 4 bar
Connection G 1 ½” AG
Chilled water circuit
Volume flow rate 2.90 m³/h
Available delivery head 630 mbar
Max. operating pressure 4 bar
Connection G 1 ¼” AG
Components
Controller Resol DeltaSol® MX (optional Siemens Climatix)

eCoo 10X

Article no. A700040

Application range
Hot water temperature 50 – 95°C
Re-cooling water temperature 22 – 40°C
Chilled water temperature 8 – 21°C
Performance data
Cooling capacity bis zu 25 kW
COPTH* max. 0.65
Dimensions
W x D x H 875 mm x 765 mm x 2.500 mm
Footprint 0.67 m2
Hot water circuit
Volume flow rate 3.75 m³/h
Available delivery head 296 mbar
Max. operating pressure 4 bar
Connection G 2″ AG
Electrical power consumption / connection
At pressure drop 511 W
At max. delivery head 911 W
Electrical connection 230 V, 50/60 Hz
Weight
Weight (empty) ca. 550 kg*
Re-cooling circuit
Volume flow rate 7.65 m³/h
Available delivery head 309 mbar
Max. operating pressure 4 bar
Connection G 2″ AG
Chilled water circuit
Volume flow rate 4.35 m³/h
Available delivery head 492 mbar
Max. operating pressure 4 bar
Connection G 2″ AG
Components
Controller Siemens Climatix

eCoo 10X ST

Application range
Hot water temperature 50 – 95°C
Re-cooling water temperature 22 – 40°C
Chilled water temperature 8 – 21°C
Performance data
Cooling capacity bis zu 25 kW
COPTH* max. 0.65
Dimensions
W x D x H 875 mm x 1.465 mm x 2.004 mm
Footprint 1.28 m2
Hot water circuit
Volume flow rate 3.75 m³/h
Available delivery head 296 mbar
Max. operating pressure 4 bar
Connection G 2″ AG
Electrical power consumption / connection
At pressure drop 626 W
At max. delivery head 1.371 W
Electrical connection 230 V, 50/60 Hz
Weight
Weight (empty) ca. 700 kg*
Re-cooling circuit
Volume flow rate 8.85 m³/h
Available delivery head 470 mbar
Max. operating pressure 4 bar
Connection G 2″ AG
Chilled water circuit
Volume flow rate 4.35 m³/h
Available delivery head 492 mbar
Max. operating pressure 4 bar
Connection G 2″ AG
Components
Controller Siemens Climatix
Circuit separation integrated

eCoo 20

Article no. A700031

Application range
Hot water temperature 50 – 95°C
Re-cooling water temperature 22 – 40°C
Chilled water temperature 8 – 21°C
Performance data
Cooling capacity bis zu 33,4 kW
COPTH* max. 0.65
Dimensions
W x D x H 875 mm x 1.465 mm x 2.004 mm
Footprint 1.28 m2
Hot water circuit
Volume flow rate 5.00 m³/h
Available delivery head 400 mbar
Max. operating pressure 4 bar
Connection G 2″ IG
Electrical power consumption / connection
At pressure drop 520 W
At max. delivery head 1.368 W
Electrical connection 230 V, 50/60 Hz
Weight
Weight (empty) ca. 785 kg*
Re-cooling circuit
Volume flow rate 10.20 m³/h
Available delivery head 640 mbar
Max. operating pressure 4 bar
Connection G 2 ½” AG
Chilled water circuit
Volume flow rate 5.80 m³/h
Available delivery head 520 mbar
Max. operating pressure 4 bar
Connection G 2″ IG
Components
Controller Siemens Climatix

eCoo 20X

Application range
Hot water temperature 50 – 95°C
Re-cooling water temperature 22 – 40°C
Chilled water temperature 8 – 21°C
Performance data
Cooling capacity bis zu 50 kW
COPTH* max. 0.65
Dimensions
W x D x H 875 mm x 1.465 mm x 2.500 mm
Footprint 1.28 m2
Hot water circuit
Volume flow rate 7.50 m³/h
Available delivery head 287 mbar
Max. operating pressure 4 bar
Connection DN 40
Electrical power consumption / connection
At pressure drop 1.022 W
At max. delivery head 1.822 W
Electrical connection 230 V, 50/60 Hz
Weight
Weight (empty) ca. 1,152 kg*
Re-cooling circuit
Volume flow rate 15.30 m³/h
Available delivery head 282 mbar
Max. operating pressure 4 bar
Connection DN 65
Chilled water circuit
Volume flow rate 8.70 m³/h
Available delivery head 481 mbar
Max. operating pressure 4 bar
Connection DN 50
Components
Controller Siemens Climatix

eCoo 30 ST

Article no. A700033

Application range
Hot water temperature 50 – 95°C
Re-cooling water temperature 22 – 40°C
Chilled water temperature 8 – 21°C
Performance data
Cooling capacity bis zu 50 kW
COPTH* max. 0.65
Dimensions
W x D x H 875 mm x 1.865 mm x 2.004 mm
Footprint 1.63 m2
Hot water circuit
Volume flow rate 7.50 m³/h
Available delivery head 870 mbar
Max. operating pressure 4 bar
Connection G 2″ IG
Electrical power consumption / connection
At pressure drop 645 W
At max. delivery head 2.140 W
Electrical connection 230 V, 50/60 Hz
Weight
Weight (empty) ca. 1,330 kg*
Re-cooling circuit
Volume flow rate 17.70 m³/h
Available delivery head 830 mbar
Max. operating pressure 4 bar
Connection G 2″ IG
Chilled water circuit
Volume flow rate 8.70 m³/h
Available delivery head 840 mbar
Max. operating pressure 4 bar
Connection G 2″ IG
Components
Controller Siemens Climatix
Circuit separation integrated

eCoo 30X

Article no. A700042

Application range
Hot water temperature 50 – 95°C
Re-cooling water temperature 22 – 40°C
Chilled water temperature 8 – 21°C
Performance data
Cooling capacity bis zu 75 kW
COPTH* max. 0.65
Dimensions
W x D x H 875 mm x 2.161 mm x 2.500 mm
Footprint 1.89 m2
Hot water circuit
Volume flow rate 11.25 m³/h
Available delivery head 282 mbar
Max. operating pressure 4 bar
Connection DN 50
Electrical power consumption / connection
At pressure drop 1.543 W
At max. delivery head 2.743 W
Electrical connection 230 V, 50/60 Hz
Weight
Weight (empty) ca. 1,728 kg*
Re-cooling circuit
Volume flow rate 22.95 m³/h
Available delivery head 278 mbar
Max. operating pressure 4 bar
Connection DN 80
Chilled water circuit
Volume flow rate 13.05 m³/h
Available delivery head 476 mbar
Max. operating pressure 4 bar
Connection DN 65
Components
Controller Siemens Climatix

eCoo 40X

Article no. A700043

Application range
Hot water temperature 50 – 95°C
Re-cooling water temperature 22 – 40°C
Chilled water temperature 8 – 21°C
Performance data
Cooling capacity bis zu 100 kW
COPTH* max. 0.65
Dimensions
W x D x H 875 mm x 2.930 mm x 2.500 mm
Footprint 2.56 m2
Hot water circuit
Volume flow rate 15.00 m³/h
Available delivery head 280 mbar
Max. operating pressure 4 bar
Connection DN 65
Electrical power consumption / connection
At pressure drop 2.064 W
At max. delivery head 3.664 W
Electrical connection 230 V, 50/60 Hz
Weight
Weight (empty) ca. 2,300 kg*
Re-cooling circuit
Volume flow rate 30.60 m³/h
Available delivery head 271 mbar
Max. operating pressure 4 bar
Connection DN 80
Chilled water circuit
Volume flow rate 17.40 m³/h
Available delivery head 472 mbar
Max. operating pressure 4 bar
Connection DN 65
Components
Controller Siemens Climatix